38kV Meta-Clad Switchgearr comes with vacuum circuit breakers, and it can be custom engineered for a range of indoor and outdoor setups. You've got a few flexible configuration options to pick from, including single aisle layouts, common aisle layouts, or full integration into a Power Control Center. This kind of control center usually holds transformers, low voltage AC or DC switchgear,and all the necessary support systems right alongside it.

|
|
|
|
||
|
ZN85A-40 3AH3 |
SF1/SF2 |
|||
|
40.5 |
||||
|
185 |
||||
|
Power Frequency Withstand Voltage(1 min) |
95 |
|||
|
50 |
||||
|
A |
1250;1600;2000 |
630;1250;2500 |
||
|
Rated Short-Circuit Breaking Current |
20,25,31.5 |
25,31.5 |
||
|
Rated Short-Circuit Making Current(Peak) |
50,63,80 |
63,80 |
||
|
50,63,80 |
63,80 |
|||
|
4s Thermal Current(RMS) |
20,25,31.5 |
25,31.5(3s) |
||
|
36-60 |
<= 45 |
|||
|
40-90 |
<= 75 |
|||
|
O-0.3s-CO-180s-CO |
||||
Uses those advanced vacuum circuit breakers.
Compartmentalized construction,so each device gets its own breaker compartment,nice and separated.
Load and incoming connections are at the back,which makes for easy access.
Works for indoor or outdoor applications,and you can choose between non walk-in or walk-in enclosures depending on what you need.
Q1: What are the applicable environmental conditions for this switchgear?
A: This product is designed to handle a pretty standard range of conditions.Ambient temperature wise,it will run fine anywhere from minus 10 to plus 40 degrees Celsius.Altitude shouldn't go above 1000 meters above sea level.For humidity,the daily average needs to stay under 95 percent,and the monthly average under 90 percent.You also want to avoid placing it where there's corrosive gases,heavy pollution,flammable gases,or a lot of intense vibration.On the seismic side,it can safely handle areas where the earthquake intensity doesn't exceed magnitude 8 on the MSK scale.
Q2: What defines "metal-clad" construction at 38kV?
A: So according to IEEE C37.20.2,for something to be called metal clad,it needs to have draw-out circuit breakers,grounded metal barriers between the major compartments,and all the live parts have to be fully enclosed in grounded metal.Our 38kV Meta-Clad Switchgear checks all those boxes,with individually grounded steel compartments for the breakers,the bus,and the cables.
Q3: What are the standard ratings available?
A: For standard ratings,you're looking at continuous current from 1200 amps up to 3000 amps,short-circuit interrupting ratings going as high as 40kA symmetrical,and a basic impulse level,or BIL,of 150 kilovolts peak.And if you need to push the continuous current even further,forced cooling options are available to extend that capability.
Popularni tagovi: 38kv meta-clad switchgear, China 38kv meta-clad switchgear manufacturers, factory, 27kV metalna zatvorena razvodna oprema, 35kV razvodna oprema, KYN28 24 razvodna oprema, Metalni zatvoreni prekidači za prekid opterećenja, Prekidači montirani na platformi, TZZB 12 razvodna oprema